Generator set data sheet
- Engine Specifications 1.500 r.p.m.
- Rated Engine Output: 2200kW prp ; 2420kW standby
- Manufacturer: MTU
- Model: 20V4000G14F
- Engine Type: 4-stroke diesel
- Injection Type: Direct
- Aspiration Type: Turbocharged and after-cooled
- Number of cylinders and arrangement: 20-V
- Bore and Stroke: 170 x 210 mm
- Displacement: 95,4 L
- Cooling System: Water
- Lube Oil Specifications: S10 W40
- Compression Ratio: 16,5:1
- Fuel Consumption ESP: 543,09 l/h
- Fuel Consumption 100% PRP: 498,84 l/h
- Fuel Consumption 75 % PRP: 385,64 l/h
- Fuel Consumption 50 % PRP: 272,44 l/h
- Fuel Consumption 25 % PRP: 156,69 l/h
- Lube oil consumption with full load: 1 % of fuel consumption
- Total oil capacity including tubes, filters 390 L
- Total coolant capacity: 790 L
- Governor Type Electrical
- Air Filter Type Dry
- Inner diameter exhaust pipe: 251 mm
- Electronic management (ADEC)
- Low coolant level sensor
- Exhaust gas compensator
- Diesel engine
- 4-stroke cycle
- Water-cooled
- 24V electrical system
- Standard air filter
- Standard fuel filter
- Standard oil filter
- Radiator with pusher fan
- HTW sender
- LOP sender
- Hot parts protection
- Moving parts protection
- Generator: MECC ALTE
- Model: ECO46.2L4A
- Poles: 4
- Connection type (standard): Star - Parallel
- Mounting type: S-00 21"
- Insulation: H class
- Enclosure (according IEC-34-5): IP23
- Exciter system: Self-excited, brushless
- Voltage regulator: A.V.R. (Electronic)
- Bracket type: Double drive-shaft
- Coupling system: Elastic Coupling
- Coating type: Standard (Vacuum impregnation)
- - OPEN SET VERSION.
- Steel chassis
- Emergency stop button
- Oil sump extraction kit
- Anti-vibration shock absorbers
- Chassis with integrated fuel tank
- Fuel level gauge
- Fuel tank drain plug
- Fuel transfer pump (Optional)
- Steel industrial silencer -15db(A) attenuation (Optional)
- Steel residential silencer -35db(A) attenuation. (Optional)
- - ELECTRICAL SYSTEM.
- Electric control and power panel with measurements devices and control unit (according to necessity and configuration)
- Connection panel wired to the safety protection (open thermal magnetic protection and alarm)
- Maintenance-free and anti-explosion battery
- Battery Switch
- Battery charger (standard on gensets with automatic control panels)
- Heating resistor (standard on sets with automatic control panels)
- Battery charger alternator with ground connection
- Starter battery/ies installed (cables and bracket included)
- Ground connection electrical installation with connection ready for ground spike (not supplied)
- - EXHAUST SYSTEM.
- Maximum exhaust temperature: 530 ºC
- Exhaust Gas Flow: 438 m3/min
- Maximum allowed back pressure: 85 mbar
- - NECESSARY AMOUNT OF AIR.
- Intake air flow: 9720 m3/h
- Cooling Air Flow: 43,63 m3/s
- Alternator fan air flow: 2,25 m3/s
- - STARTING SYSTEM.
- Starting power: 7,5 x 2 kW
- Starting power: 10,2 x 2 CV
- Recommended battery: 400 Ah
- Auxiliary Voltage: 24 Vdc
- - FUEL SYSTEM
- Fuel Oil Specifications: Diesel
- - DIMENSIONS.
- Length: 7.300 mm
- Height: 2.762 mm
- Width: 2.280 mm
- Maximum shipping volume: 45,97 m3
- Weight with liquids in radiator and sump: 18.950 kg
Length (A)730287.40
Width (B)22889.76
Height (C)276.2108.74
Weight with fluids in radiator and crankcase
18950
41784.75